APPENDIX A: TROUBLESHOOTING
The following is a guide to troubleshooting, using the Summit 3208GLD security system.
Problem Reason Action
Telephone line failure appears
when the telephone line is not
connected (control panel used as a
local alarm).
Event codes programmed at
values above “00”.
Program event codes as “00” and
power down the panel.
Keypad display not responsive. A Keypad at a different address
has been activated.
Wait for time out to activate, or
press “AWAY” key.
No display on keypad. Auxiliary power fuse blown. Replace fuse.
Constant low battery message on
display.
Faulty battery or battery fuse
blown.
Replace battery at least every five
years or replace the blown fuse.
No sound from the bell. Blown bell fuse or wrong
parameters.
Replace fuse or program the bell
parameters correctly.
Zone expander does not give any
zone indications.
Zone expander supervision is not
programmed.
Reprogram parameters.
A single output does not react
properly.
Programming error. Correct the programming for the
specific relay.
Wrong alarm or trouble indicator
from the zone.
Wrong zone loop type selected. Reprogram zone type parameters
for the correct loop type.
Failure to communicate with the
central station.
Wrong telephone number, wrong
event code, wrong protocol, or
wrong telephone line parameters.
Consult with the central station
owner/operator and program the
appropriate parameters.
Failure to communicate with the
central station.
Incorrect telephone line
communication.
Incoming line should be connected
to terminals 3 and 4. Outgoing
telephone line to terminals 1 and 2.